Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
Physical Address
304 North Cardinal St.
Dorchester Center, MA 02124
ANSI B149.6-15 (also designated CSA B149.6-15) is a joint American National Standard and Canadian Standards Association code that establishes minimum requirements for the design, construction, and installation of natural gas–fuelled electric power generating stations. The standard applies to stationary engine and turbine installations that use natural gas as the primary fuel, including both simple-cycle and combined-cycle configurations, as well as combined heat and power (CHP) systems.
Formally titled “Code for the design, construction, and installation of natural gas fuelled electric power generating stations,” ANSI B149.6-15 was published in 2015 and remains current for new installations. It is referenced by many North American jurisdictional authorities and is commonly adopted alongside the National Fuel Gas Code (NFPA 54) and the CSA B149 series of gas installation codes. The 2015 edition supersedes earlier editions and includes updated provisions for combustion air, ventilation, gas detection, and electrical classification.
This code covers:
ANSI B149.6-15 prescribes detailed engineering requirements organized into several key categories. The following subsections highlight the most significant technical provisions.
The standard requires that generating stations be located in areas that minimize risk to persons and property. Minimum separation distances are specified between the station building or outdoor enclosure and adjacent buildings, property lines, public ways, and flammable liquid storage. Table 1 below summarizes the key spacing requirements from Table 4.1 of the standard for typical installations.
| Exposure | Minimum Distance (ft) | Minimum Distance (m) |
|---|---|---|
| Building openings (windows, doors, vents) on the same property | 10 | 3.0 |
| Property line or public way | 25 | 7.6 |
| Flammable liquid storage (e.g., day tanks) | 10 | 3.0 |
| Above-ground flammable gas piping (other than station piping) | 15 | 4.6 |
| Ignition sources within classified areas | per area classification | per area classification |
All gas piping, regulators, meters, and pressure-limiting devices must comply with the applicable sections of CSA B149.1 (for Canada) or NFPA 54 (for the U.S.) as minimums. The code mandates a manual shutoff valve at the station boundary, a pressure regulator capable of delivering gas at the required pressure and capacity, and a safety shutoff valve that closes automatically upon detection of abnormal conditions (e.g., loss of flame, overpressure, gas leak). Emergency shutdown (ESD) controls must be clearly marked and accessible.
One of the most critical sections deals with ventilation of indoor generator enclosures. The standard requires that ventilation systems be designed to limit the accumulation of flammable gas to 25 % of the lower flammable limit (LFL) in any enclosed or semi-enclosed area under normal and abnormal conditions. For engine-driven generators, the combustion air supply must be sufficient to support the maximum continuous rating of the engine plus any auxiliary combustion sources within the same space.
Electrical installations must meet the requirements of the Canadian Electrical Code (CSA C22.1) or the U.S. National Electrical Code (NFPA 70) as applicable. The standard defines Class I, Division 1 and Division 2 areas around gas components. It also mandates:
Before construction, the designer or owner must conduct a risk assessment considering the location, fuel supply characteristics, and potential failure modes. This assessment forms the basis for determining ventilation rates, gas detection thresholds, and ESD response times. The standard recommends that the risk assessment be reviewed and updated whenever the station configuration or fuel characteristics change.
ANSI B149.6-15 requires a formal commissioning plan that includes:
ANSI B149.6-15 is adopted by reference in many U.S. states and Canadian provinces. Designers and installers should verify that the adopted edition matches the project’s jurisdiction. Some authorities may add amendments—for example, requiring seismic bracing of gas piping in earthquake-prone areas or stricter emission limits. The standard itself does not address emissions; those are covered by local air quality regulations.
The code does not prescribe maintenance intervals, but it does require that the owner maintain the installation “in a safe operating condition” per the manufacturer’s instructions and the original design basis. Regular inspections of gas detection systems, ventilation fans, and safety shutoff valves are expected. Annual testing of automatic shutdowns is a common industry practice.
In summary, ANSI B149.6-15 provides a comprehensive safety framework for natural gas–fuelled power generating stations. By following its requirements for siting, fuel gas supply, ventilation, and electrical safety, designers, owners, and operators can significantly reduce the risk of fire, explosion, and gas exposure. The standard is an essential reference for anyone involved in the planning, construction, or operation of natural gas power generation facilities.
© 2026 International Standards Publishing. All rights reserved.