📘 ASME B31Ea-2010 is the official Addenda to ASME B31E-2008, “Standard for the Seismic Design and Retrofit of Above-Ground Piping Systems.” It was approved by the American National Standards Institute (ANSI) on May 13, 2010, after approval by the ASME B31 Committee and ASME, and issued on July 6, 2010. The Addenda is published in its entirety for the user’s convenience; every change is identified on the affected pages by a margin note (a). For organizations implementing seismic design and retrofit projects, the practical meaning is direct: any project citing B31E-2008 should be updated to the B31Ea-2010 content, or calculations will be performed with superseded data.
According to the Summary of Changes at the front of the Addenda, the revisions concentrate on two clauses and one table, plus reference updates:
| Page | Location | Change | Nature |
|---|---|---|---|
| 2 | 3.1 | Revised | Technical revision |
| 2 | 3.3.1 | (1) Both equations revised; (2) “238 MPa” in the last paragraph revised to “240 MPa” | Technical revision / correction |
| 3 | Table 2 | Revised (maximum span between lateral seismic restraints) | Technical revision |
| 5 | 7 | (1) First paragraph revised; (2) references updated | Technical revision |
The Addenda does not change the scope, the terminology system, or the overall methodology of the Standard — it remains aimed at above-ground metallic piping systems in the scope of the B31 sections, with the three-tier seismic functional goals of position retention, leak tightness, and operability. The changes lie at the level of design calculation detail and reference data.
Section 3.1 of Chapter 3 (Design) was revised in its entirety. In the original B31E-2008, Section 3.1 states the basic requirements and applicability of seismic design (for example, that the piping system must comply with the applicable B31 section, and that seismic loads are treated as occasional loads). The revision clarifies and sharpens these design statements based on engineering feedback, tying them more tightly to the calculation details of Section 3.3.
Users should treat any design-document reference to “3.1” as referring to the post-Addenda text. This means that citation numbers and wording regarding seismic load treatment, analysis, and verification premises in existing design documentation should be rechecked in updated documents.
Section 3.3.1 is the technical core of this Addenda. It contains the two equations used for restraint design and verification under seismic loading (the Summary of Changes states that both equations were revised). Although the specific equation forms are not reproduced in the summary, the overall framework makes it clear that:
At the same time, the last paragraph of 3.3.1 corrects “238 MPa” to “240 MPa.” This value is the metric conversion of the steel pipe yield stress stated in the heading of Table 2: 35 ksi × 6.89476 ≈ 241.3 MPa, rounded to 240 MPa. The original 238 MPa was a rounding error in the conversion; the Addenda corrects it. The correction directly affects the applicability premise of Table 2 — when using the restraint spacing table under metric conditions, the premise is now “yield stress 240 MPa.”
Table 2 gives the maximum span (ft/m) between lateral seismic restraints for steel pipe with a yield stress of 35 ksi (240 MPa), in water service at 70°F (21°C). The Addenda revises Table 2 in its entirety, adjusting the maximum spans for the various pipe sizes.
Since restraint spacing is the parameter most often used directly in seismic design, the Table 2 revision has immediate engineering significance:
It bears repeating that Table 2 is a reference for specific conditions: steel pipe, water service, 70°F, with the corresponding seismic input and allowable-stress premises implied. For other materials, fluids, temperatures, or seismic parameters, analysis per Chapter 3 is still required; values cannot be extrapolated directly.
Section 7 (References) had its first paragraph revised and its reference list updated. References in the B31 family typically include the ASME B31 sections, ASCE seismic codes and ground-motion sources, and the provisions on seismic effects in the model building code system (IBC/ASCE 7). Updating the references keeps the Addenda aligned with the then-current code system — in particular, the sources for seismic input parameters (seismic zoning, site class, and response spectrum parameters in ASCE 7) may have changed with newer editions.
Two direct effects on practice follow: first, seismic input parameters (design response spectrum, site class, importance factor) should be taken from the reference editions updated by the Addenda, keeping input and verification methodology version-consistent; second, the reference lists quoted in design documents should be updated to avoid “mixed old-and-new edition” disputes during review.