📡 BS EN 55016 is the British adoption of the CENELEC series EN 55016, which is identical to the CISPR 16-1 series of international standards. The series specifies the measuring instruments, coupling devices, antennas and test sites used to measure radio disturbance (emission) and immunity (susceptibility), together with the measurement procedures and the evaluation of measurement uncertainty. It is one of the most frequently applied basic EMC standards for type testing, product certification, and laboratory accreditation.
The BS EN 55016 series is organised into three functional blocks: Part 1 (measuring apparatus, corresponding to CISPR 16-1), Part 2 (measurement methods, corresponding to CISPR 16-2) and Part 4 (measurement uncertainty, corresponding to CISPR 16-4). The sub-parts in this batch cover:
| Standard | Main Content | CISPR Equivalent |
|---|---|---|
| BS EN 55016-1-1:2010+A2:2014 | Measuring apparatus — requirements for disturbance and immunity measurement equipment | CISPR 16-1-1 |
| BS EN 55016-1-2:2014 | Measuring apparatus — coupling devices for conducted disturbance measurements | CISPR 16-1-2 |
| BS EN 55016-1-4:2010+A1:2012 | Measuring apparatus — antennas and test sites for radiated disturbance measurements | CISPR 16-1-4 |
| BS EN 55016-1-5:2015 | Antenna calibration and test sites for 30 MHz to 1000 MHz | CISPR 16-1-5 |
| BS EN 55016-1-6:2015 | Validation of anechoic chambers | CISPR 16-1-6 |
| BS EN 55016-2-1:2014 | Conducted disturbance measurement methods (AMN) | CISPR 16-2-1 |
| BS EN 55016-2-2:2011 | Measurement of disturbance power (CDNE/ISN) | CISPR 16-2-2 |
| BS EN 55016-2-3:2010+A2:2014 | Radiated disturbance measurement methods (antennas and sites) | CISPR 16-2-3 |
| BS EN 55016-2-4:2004 | Immunity measurement methods (conducted and radiated) | CISPR 16-2-4 |
| BS EN 55016-4-2:2011+A1:2014 | Uncertainty in EMC measurements (statistical treatment) | CISPR 16-4-2 |
Part 1-1 specifies the technical requirements for disturbance measuring receivers (quasi-peak, average and RMS detectors), artificial mains networks (AMNs), voltage probes, current probes and absorbing clamps, covering frequency range, input impedance, detector characteristics, bandwidth, and overload capability, together with calibration and periodic check requirements. Measured results are only comparable when the apparatus meets these specifications.
Part 1-2 deals specifically with coupling devices for conducted disturbance measurements, including artificial mains networks, impedance stabilisation networks (ISNs) and common-mode termination networks. It is worth noting that, at the 2014 revision, the UK voted against approval, expressing concern that clause 9 (CDNE-M) does not provide a representative simulation of mains cabling — an illustration that the standard continues to evolve in engineering practice.
Part 1-4 specifies the antennas and test sites used for radiated disturbance measurements, covering antenna factors, site attenuation, open-area test sites (OATS) and anechoic chamber requirements, and adds provisions for the evaluation of a set-up table above 1 GHz. Parts 1-5 and 1-6 provide antenna calibration methods and chamber validation procedures respectively.
Part 2 provides uniform test set-ups, procedures and reporting rules according to the type of disturbance and the object under test:
Part 4-2 gives the method for evaluating EMC measurement uncertainty, expressing results as “measured value ± expanded uncertainty”. It systematically analyses uncertainty contributions such as receiver error, antenna factor, cable loss, site factors and set-up repeatability, and provides the statistical procedures for combination and expansion. For conformity assessment, uncertainty must be taken into account so that the inherent error of the measurement system does not cause erroneous pass/fail decisions.