PD IEC TR 60919 — Performance of High-Voltage Direct Current (HVDC) Systems with Line-Commutated Converters Technical Report Series

Performance of High-Voltage Direct Current (HVDC) Systems with Line-Commutated Converters

⚡ PD IEC TR 60919 is the British Standards Institution (BSI) Published Document implementing the International Electrotechnical Commission (IEC) technical report IEC/TR 60919, addressing the performance of high-voltage direct current (HVDC) transmission systems with line-commutated converters (LCC). Prepared by the UK technical committee PEL/22 “Power electronics” and classified under ICS 29.200 (rectifiers, converters) and 29.240.99 (other transmission and distribution equipment), the series provides technical guidance on steady-state/dynamic performance, faults and switching, and AC-side dynamic voltage control — a key basis for HVDC system design, operation, and performance evaluation.

💡 HVDC transmission offers advantages for large-capacity, long-distance transmission and grid interconnection, but its converters interact with the AC grid in complex ways. These technical reports give designers and operators a unified method for assessing steady-state operation, fault response, and voltage control.

1. Series Structure and Overall Framework 📌

The PD IEC TR 60919 series consists of 3 parts, covering steady-state and dynamic performance, faults and switching, and AC-side dynamic voltage control. Parts 1 and 2 were updated by IEC amendments A1 (2013 and 2015).

PartYearTitleCore Content
PD IEC/TR 60919-1 (+A1)2010 (+2013)Steady-state and dynamic performanceSpecifies HVDC system types and steady-state, dynamic performance requirements
PD IEC/TR 60919-2 (+A1)2008 (+2015)Faults and switchingSpecifies system fault characteristics and performance under switching operations
PD IEC/TR 60919-32009AC-side dynamic voltage controlSpecifies AC-side dynamic voltage control and interaction with reactive power sources
⚠️ This series is an IEC/TR technical report of reference nature, not a mandatory standard. Always reference the current BSI version (including amendments) and consider relevant HVDC standards and grid codes.

2. Steady-State and Dynamic Performance: Part 1 Requirements ⚙️

Part 1 specifies the types of HVDC systems and their steady-state and dynamic performance requirements:

  • HVDC system types: includes back-to-back systems, point-to-point transmission, and bipolar/monopolar topologies.
  • Steady-state performance: specifies converter current, voltage, power, and power-factor characteristics under normal operation.
  • Dynamic performance: specifies dynamic response and stability under disturbances and load changes.
  • Control characteristics: describes converter control (e.g., constant-current, constant-power, constant-extinction-angle) and its effect on performance.

Part 1 also specifies performance assessment criteria and test-verification methods for system design and acceptance.

3. Faults and Switching: Part 2 Requirements 🚨

Part 2 specifies the performance and response of HVDC systems under faults and switching:

ItemDescription
DC-side faultsCurrent and voltage response and protection action for DC line and converter valve faults
AC-side faultsCommutation failure, power fluctuation, and recovery characteristics caused by AC grid faults
SwitchingBehaviour during converter switching, pole start/stop, and power reversal
Protection and recoverySpecifies protection strategy and post-fault recovery requirements

Part 2 focuses on converter-grid interaction during faults and operations, providing reference for protection setting and operating-mode arrangement.

4. AC-Side Dynamic Voltage Control: Part 3 Requirements 📉

Part 3 specifies the AC-side dynamic voltage control of an HVDC converter station and its interaction with reactive power sources:

ItemDescription
Converter as active/reactive power sourceAnalyses the voltage characteristics of the converter as an active/reactive power source
AC network voltage characteristicsAnalyses AC network voltage characteristics based on loading at the HVDC substation busbar
AC filters, capacitor banks, and shunt reactorsAnalyses the effect of filters, capacitor banks, and shunt reactors on voltage/reactive characteristics
Dynamic voltage control strategySpecifies voltage-control and reactive-regulation strategies and coordination

Part 3 helps designers assess voltage stability and reactive balance after connecting an HVDC converter station to the AC grid, ensuring safe operation.

✅ The three parts form a complete specification for LCC-HVDC system performance: Part 1 on “steady-state and dynamic performance,” Part 2 on “faults and switching,” and Part 3 on “AC-side voltage control,” together supporting DC transmission design and operation assessment.

5. Engineering Practice and Application Notes 🛠️

  • 🔍 System design: choose topology and control strategy per Part 1 to meet steady-state and dynamic performance requirements.
  • 🔧 Protection setting: analyse fault characteristics per Part 2 to set protection and recovery logic appropriately.
  • 📊 Reactive and voltage planning: configure filters, capacitors, and reactors per Part 3 to maintain voltage stability.
  • 📋 Comparison with IGBT/VSC technology: this series targets line-commutated converters (LCC); voltage-source-converter (VSC-HVDC) using fully controlled devices has a separate standard system.

6. Frequently Asked Questions ❓

❓ Q: What is line-commutated converter (LCC) HVDC?
A: LCC-HVDC uses thyristor converter valves and relies on AC grid commutation; it is the mainstream technology for large-capacity, long-distance DC transmission, such as back-to-back and point-to-point projects.
❓ Q: Why does HVDC need attention to AC-side voltage control?
A: The converter both absorbs and generates reactive power during operation, interacting with the AC grid, filters, and reactive compensation equipment, affecting voltage stability and requiring coordinated control.
❓ Q: What is commutation failure?
A: Commutation failure is where an AC-side voltage disturbance prevents converter valves from commutating in sequence, causing a DC current surge and power drop; it is a typical LCC-HVDC fault requiring protection and control measures.
🔍 Q: Why is this series published as a Technical Report (TR)?
A: Because it is an IEC technical report providing system-performance evaluation and design guidance rather than mandatory requirements, for reference in DC transmission engineering design and operation.
🔒