🚰 BS EN 806 is the UK implementation of European Standard EN 806, titled “Specifications for installations inside buildings conveying water for human consumption”. UK participation is held by Subcommittee B/504/2 (Internal systems and components / Domestic installation design — internal) under Technical Committee B/504 (Water supply). It is the European-level family of standards governing the design, sizing, installation, and operation and maintenance of internal drinking-water distribution systems in buildings. The series was published as a “package” with a common date of withdrawal and partially supersedes the former UK code BS 6700:1997.
💡 All parts of BS EN 806 belong to the package: Part 1 general, Part 2 design, Part 3 pipe sizing, Part 4 installation, and Part 5 operation and maintenance — they must be used together to form a complete technical file for a building water-supply system. BS 6700:1997 is progressively withdrawn as the parts are published.
1. Series Structure and Document Overview 📋
This batch contains five standard documents published between 2000 and 2012 — three readable and two scanned.
| Standard | Subject | Status |
| BS EN 806-1:2000 + A1:2001 (2002) | General | Readable (includes amendment A1:2001) |
| BS EN 806-2:2005 | Design | Readable (partially supersedes BS 6700) |
| BS EN 806-3:2006 | Pipe sizing | Readable (partially supersedes BS 6700) |
| BS EN 806-4:2010 | Installation | Scanned copy — written from public-domain knowledge |
| BS EN 806-5:2012 | Operation and maintenance | Scanned copy — written from public-domain knowledge |
⚠️ BS EN 806-4:2010 and BS EN 806-5:2012 in this batch are scanned copies whose full text could not be machine-recognized. Their content is summarized here from public-domain knowledge; consult the official BSI editions for definitive clauses.
2. General Requirements: BS EN 806-1:2000+A1:2001 📘
BS EN 806-1 is the foundation of the series; it defines general requirements for drinking-water distribution systems inside buildings:
- Terms and definitions: drinking water, distribution system, draw-off point, etc.;
- Water-quality preservation: principles to prevent water degradation (flow, temperature control, avoiding stagnant dead legs);
- Material and component compatibility: materials in contact with drinking water must not impair water quality (in line with food-contact requirements);
- General principles of backflow prevention: isolation from contaminated sources and backflow-protection principles;
- General design and construction requirements: pipe routing, support, frost protection, and accessibility for maintenance.
⚠️ Water-quality preservation runs through the whole series: prolonged stagnation and water temperatures within bacterial growth ranges (e.g., Legionella) are major risks. Design should avoid dead legs, provide circulation and drain points where needed, and manage water temperature in operation.
3. Design: BS EN 806-2:2005 📐
BS EN 806-2 specifies design methods and requirements for internal drinking-water distribution systems:
- Determination of water demand and simultaneous-use (loading) probability;
- Choice of system type (direct supply, tank supply, booster-pump supply, etc.);
- Pipework layout principles (mains, risers, branches, valves and maintenance points);
- Pressure requirements (minimum and maximum working pressures, static and dynamic);
- Temperature design against microbiological risks such as Legionella (hot-water system requirements);
- Principles for backflow protection, filters, metering, and water-quality monitoring devices.
💡 Design leads the series: the outputs of BS EN 806-2 (system type, flow, pressure, preliminary sizes) are the inputs of Part 3 sizing and Part 4 installation. Consider future retrofit and maintenance accessibility at design stage to avoid “built once, hard to change later”.
4. Pipe Sizing: BS EN 806-3:2006 📏
BS EN 806-3 specifies methods for sizing drinking-water distribution pipes:
- Sensible velocity ranges and limits (to prevent noise, water hammer, and excessive pressure drop);
- Calculation of friction (head loss) and local losses (using the corresponding hydraulic formulae/tables);
- Application of simultaneous-use probability in sizing;
- Minimum delivery pressure requirements (pressure needed at the appliance);
- Handling of reductions and branch connections in the calculation.
🚨 Pipes too small cause inadequate end pressure, noise, and cavitation; pipes too large run at low velocity with long stagnation and higher water-quality risk. Sizing must balance flow, velocity, pressure drop, and water age, and account for how water-saving fittings lower flow and increase age.
5. Scanned Sectional Parts (BS EN 806-4 and BS EN 806-5) 🔍
BS EN 806-4:2010 specifies installation requirements for drinking-water systems: joining methods for pipes and fittings, supports and fixing, wall penetration and fire-stopping, pressure testing and flushing/disinfection, and system acceptance — the field-implementation clauses. BS EN 806-5:2012 specifies operation and maintenance requirements: commissioning, routine operational checks, water-quality monitoring, pipe flushing, backflow-device maintenance, and fault handling. Both documents are scanned copies, summarized here from public-domain knowledge.
💡 Installation and operation turn the “design on paper” into a “qualified real system”: pressure testing and flushing/disinfection must be recorded, and the operation-and-maintenance plan should define flushing frequencies, temperature-monitoring points, and water-quality sampling schedules.
6. Engineering Practice Essentials 🛠️
- 🔍 Design workflow: determine water demand and simultaneous-use factor → choose system form and layout per BS EN 806-2 → size pipes and pressures per BS EN 806-3 → add backflow and temperature-control measures → prepare material lists and instructions.
- 🔧 Site installation: join, support, pressure-test, flush, and disinfect per BS EN 806-4; accept and record the results.
- 📊 Operation and maintenance: establish operational checks, water-quality monitoring, and flushing plans per BS EN 806-5, focusing on temperature and stagnation age.
- 📋 Documentation: archive design calculations, as-built drawings, pressure-test/flushing records, water-test reports, and maintenance logs.
✅ Practice note: use the BS EN 806 series with the relevant pipe product standards, backflow-prevention standards (following EN 1717 principles), and local drinking-water regulations to form a complete quality loop from design, through construction, to operation.
7. Frequently Asked Questions ❓
❓ Q: What is the relationship between BS EN 806 and BS 6700?
A: BS 6700:1997 was the former UK code for building water-supply design and installation. The BS EN 806 series progressively replaces it; as each part is published it supersedes the corresponding clauses, and BS 6700 is finally withdrawn. The UK keeps certain national annexes on top of BS EN 806 to link with local practice.
❓ Q: Why control water velocity in pipe sizing?
A: Excessive velocity causes noise, water hammer, and pressure drop; too-low velocity lengthens stagnation and degrades water quality. BS EN 806-3 sets a sensible velocity range for a quiet, efficient installation with good water quality.
❓ Q: How is Legionella risk managed in drinking-water systems?
A: Mainly by temperature and flow management: control cold and hot water temperatures (hot-water storage and return at bacteriostatic levels), avoid dead ends, and flush infrequently used branches. BS EN 806-2 temperature design and BS EN 806-5 operational clauses together cover the risk.
🔍 Q: Why is backflow protection important?
A: If internal connections to polluted sources (boiler make-up, irrigation) are made wrongly, pressure reversal can draw contaminated water into the drinking-water system. The series requires backflow devices at risky connection points, with regular maintenance and testing.
❓ Q: Can the scanned sectional parts be used directly for design and installation?
A: Use with caution. BS EN 806-4 and BS EN 806-5 are scanned copies; verify and obtain the latest official editions from BSI before formal design and construction.