BS EN 60947 — Low-Voltage Switchgear and Controlgear Standard Series

Low-voltage Switchgear and Controlgear (BSI Adoption of IEC/EN 60947)

⚡ BS EN 60947 is the British Standards Institution’s adoption of the IEC 60947 series, harmonised in Europe as EN 60947, covering “Low-voltage switchgear and controlgear.” The series is the product and test framework for switching, control, protection and connection equipment rated at a.c. up to 1000 V and d.c. up to 1500 V, coordinated in the UK under Technical Committee PEL/17 (Switchgear, controlgear, and HV-LV co-ordination) and its subcommittee PEL/17/2. BS EN 60947-1 (General rules) is the framework; subsequent parts give particular requirements and tests for circuit-breakers, switches, disconnectors, contactors, motor-starters, control circuit devices, auxiliary equipment and terminal blocks. The series underpins industrial power distribution, building electrical systems, machine control and switchgear assemblies (used with BS EN 61439), and is the cornerstone of low-voltage product certification and export.

💡 Of the 22 documents in this series digest, only Parts 1, 2 and 3 are readable text; the rest are mostly scanned versions. Where the article summarises scanned parts, it is written from publicly available domain knowledge and marked accordingly; temperature-rise, short-circuit and dielectric test values must come from the official BSI publication.

1. Series Overview and Scope 📌

Low-voltage switchgear and controlgear are the devices that make, break, isolate, protect and control circuits in low-voltage distribution and motor-control systems, covering manual and automatic switching devices and control relays. The BS EN 60947 series defines electrical and mechanical performance, temperature rise, dielectric properties, short-circuit making and breaking capacity, operation and endurance, degree of protection and marking, and establishes a rated-value system (rated current, rated short-time withstand current, rated service short-circuit breaking capacity Ics, rated ultimate short-circuit breaking capacity Icu).

  • General rules: BS EN 60947-1 sets terminology, classification, characteristics, general test requirements and marking — the common basis for all parts.
  • Protection devices: circuit-breakers (-2), overload/short-circuit protection.
  • Switching and isolation: switches, disconnectors, fuse-combination units (-3).
  • Control devices: contactors (-4-1), motor-starters (-4-1/-4-2/-4-3), control circuit devices and switching elements (-5 series).
  • Auxiliary and connection: terminal blocks (-7 series), auxiliary equipment (-6, -8).
⚠️ Scanned version, written from publicly available domain knowledge: the parts covering contactors, motor-starters, control circuit devices (proximity switches, position switches, push-buttons, indicator lamps, relays, solenoid interfaces) and terminal blocks are largely scanned; their exact rated values, test methods and acceptance criteria must be verified against the official publication.

2. Series Structure and Part List 📋

The table lists the main parts of the BS EN 60947 series and their subjects (part numbers correspond to the digest file list).

PartSubjectContent
Part 1General rulesTerminology, characteristics, tests, marking
Part 2Circuit-breakersLow-voltage breakers (incl. short-circuit protection and breaking capacity)
Part 3Switches, disconnectors, fuse-combination unitsManual switching and isolation
Part 4-1Contactors and motor-starters — electromechanicalContactors and direct/reversing starters
Part 4-2AC semiconductor motor controllers and startersSoft-start / solid-state control
Part 4-3Controllers and contactors for non-motor loadsContactors for non-motor loads
Part 5-1Control circuit devices and switching elements — electromechanicalPosition switches, push-buttons, etc.
Part 5-2Proximity switchesNon-contact sensing switches
Part 5-3Indicator-light push-buttonsIndicating control buttons
Part 5-4Methods and equipment with separate housingSpecific installation requirements
Part 5-5Electromechanical control equipment for circuit interfacesInterface devices
Part 5-6DC interface (electromechanical)DC control interface
Part 5-7Auxiliary devices (time, threshold, etc.)Auxiliary control elements
Part 5-8Three-position switchesFoot / three-position control
Part 5-9Flow switchesFlow control
Part 6-1Multi-function equipment — transfer switchingDual-supply changeover
Part 6-2Multi-function equipment — control and protective switchesCPS-type devices
Part 7-1 to 7-4Terminal blocksTerminals for copper/aluminium conductors
Part 8Auxiliary equipment — rotating machine starter accessoriesStarter auxiliary equipment

3. Key Technical Requirements 🔧

3.1 General rules (BS EN 60947-1)

Part 1 harmonises terminology, normal service conditions, constructional requirements (free-trip, interlocking), electrical ratings (voltage, current, frequency, power factor, time-current characteristics), temperature-rise limits, dielectric and insulation resistance, performance under short-circuit conditions, endurance (mechanical and electrical), electromagnetic compatibility (EMC) and marking. It is identical to IEC 60947-1:2007 incorporating amendments 1 and 2, and is the common basis of the other parts (maintained by PEL/17/2).

3.2 Circuit-breakers (BS EN 60947-2)

This part gives particular requirements for low-voltage circuit-breakers (including combined residual-current devices). The core concerns are making and breaking capacity under short-circuit conditions, tripping characteristics (overload and short-circuit), dielectric strength and temperature rise. It defines the key indicators Icu (rated ultimate short-circuit breaking capacity) and Ics (rated service short-circuit breaking capacity), which underpin selective protection and person/equipment safety in distribution systems.

3.3 Switches and disconnectors (BS EN 60947-3)

This part covers non-automatic switches, disconnectors and fuse-combination units, emphasising isolation function (visible break, clear OFF position, protection against inadvertent closing) and safety interlocking, used for on-load switching and isolation during maintenance.

⚠️ Scanned version, written from publicly available domain knowledge: the contactor, motor-starter, control circuit device and terminal-block parts are scanned; their specific ratings (e.g. currents at AC-3 utilisation category), test voltages, creepage and clearances must be checked item by item against the official text before selection or certification.

4. Engineering Practice 🛠️

  • 🔍 Selection: choose contactors, circuit-breakers and disconnectors by utilisation category (AC-1 to AC-4, DC) and rating; verify short-circuit breaking capacity matches the system prospective short-circuit current.
  • 🔧 Assembly design: work with BS EN 61439 (switchgear assemblies) to check in-cabinet temperature rise, degree of protection and short-circuit withstand.
  • 📊 Motor control: select contactors and starters per the Part 4 series, accounting for frequent starting, reversing and soft-start needs; coordinate overload protection with thermal relays or electronic protection.
  • 📋 Marking and maintenance: equipment must be clearly marked with ratings and wiring diagrams; periodically inspect contact wear, temperature rise and trip settings.
🚨 The short-circuit breaking capacity and isolation reliability of low-voltage switchgear directly affect personnel and equipment safety. A wrong selection (e.g. breaking capacity below the prospective short-circuit current) can cause an arcing fault explosion or failure to isolate an energised circuit; design verification must be carried out by a qualified electrical engineer to current standards.

5. Frequently Asked Questions ❓

❓ Q: What is the difference between BS EN 60947 and BS EN 60898 (household breakers)?
A: BS EN 60947 is for industrial and commercial low-voltage switchgear, emphasising breaking capacity, utilisation categories and system coordination; BS EN 60898 is for overcurrent-protection circuit-breakers (MCBs) in household and similar premises. They differ in application and assessment focus and cannot be substituted one for the other.
❓ Q: What do Icu and Ics represent?
A: Icu (ultimate short-circuit breaking capacity) is the maximum short-circuit current the breaker can interrupt, after which it need not remain fit for further service; Ics (service short-circuit breaking capacity) is the level at which it can interrupt and still continue to operate normally, typically Ics ≤ Icu, and is chosen for circuits needing repeated interruption.
❓ Q: What is the significance of utilisation categories AC-3 and AC-4?
A: Utilisation categories define the making/breaking duty for contactors under different loads. AC-3 covers normal starting of squirrel-cage motors and disconnection during running; AC-4 includes difficult breaking such as inching and plugging during starting, requiring higher electrical endurance and breaking capacity.
❓ Q: Why are control circuit devices (Part 5) included in this standard?
A: Push-buttons, position switches, proximity switches, indicator lamps and relays are essential to low-voltage control systems; including them in the same standard system enables assembly design, rating coordination and unified test methods.
🔒