⚡ BS EN 60947 is the British Standards Institution’s adoption of the IEC 60947 series, harmonised in Europe as EN 60947, covering “Low-voltage switchgear and controlgear.” The series is the product and test framework for switching, control, protection and connection equipment rated at a.c. up to 1000 V and d.c. up to 1500 V, coordinated in the UK under Technical Committee PEL/17 (Switchgear, controlgear, and HV-LV co-ordination) and its subcommittee PEL/17/2. BS EN 60947-1 (General rules) is the framework; subsequent parts give particular requirements and tests for circuit-breakers, switches, disconnectors, contactors, motor-starters, control circuit devices, auxiliary equipment and terminal blocks. The series underpins industrial power distribution, building electrical systems, machine control and switchgear assemblies (used with BS EN 61439), and is the cornerstone of low-voltage product certification and export.
Low-voltage switchgear and controlgear are the devices that make, break, isolate, protect and control circuits in low-voltage distribution and motor-control systems, covering manual and automatic switching devices and control relays. The BS EN 60947 series defines electrical and mechanical performance, temperature rise, dielectric properties, short-circuit making and breaking capacity, operation and endurance, degree of protection and marking, and establishes a rated-value system (rated current, rated short-time withstand current, rated service short-circuit breaking capacity Ics, rated ultimate short-circuit breaking capacity Icu).
The table lists the main parts of the BS EN 60947 series and their subjects (part numbers correspond to the digest file list).
| Part | Subject | Content |
|---|---|---|
| Part 1 | General rules | Terminology, characteristics, tests, marking |
| Part 2 | Circuit-breakers | Low-voltage breakers (incl. short-circuit protection and breaking capacity) |
| Part 3 | Switches, disconnectors, fuse-combination units | Manual switching and isolation |
| Part 4-1 | Contactors and motor-starters — electromechanical | Contactors and direct/reversing starters |
| Part 4-2 | AC semiconductor motor controllers and starters | Soft-start / solid-state control |
| Part 4-3 | Controllers and contactors for non-motor loads | Contactors for non-motor loads |
| Part 5-1 | Control circuit devices and switching elements — electromechanical | Position switches, push-buttons, etc. |
| Part 5-2 | Proximity switches | Non-contact sensing switches |
| Part 5-3 | Indicator-light push-buttons | Indicating control buttons |
| Part 5-4 | Methods and equipment with separate housing | Specific installation requirements |
| Part 5-5 | Electromechanical control equipment for circuit interfaces | Interface devices |
| Part 5-6 | DC interface (electromechanical) | DC control interface |
| Part 5-7 | Auxiliary devices (time, threshold, etc.) | Auxiliary control elements |
| Part 5-8 | Three-position switches | Foot / three-position control |
| Part 5-9 | Flow switches | Flow control |
| Part 6-1 | Multi-function equipment — transfer switching | Dual-supply changeover |
| Part 6-2 | Multi-function equipment — control and protective switches | CPS-type devices |
| Part 7-1 to 7-4 | Terminal blocks | Terminals for copper/aluminium conductors |
| Part 8 | Auxiliary equipment — rotating machine starter accessories | Starter auxiliary equipment |
Part 1 harmonises terminology, normal service conditions, constructional requirements (free-trip, interlocking), electrical ratings (voltage, current, frequency, power factor, time-current characteristics), temperature-rise limits, dielectric and insulation resistance, performance under short-circuit conditions, endurance (mechanical and electrical), electromagnetic compatibility (EMC) and marking. It is identical to IEC 60947-1:2007 incorporating amendments 1 and 2, and is the common basis of the other parts (maintained by PEL/17/2).
This part gives particular requirements for low-voltage circuit-breakers (including combined residual-current devices). The core concerns are making and breaking capacity under short-circuit conditions, tripping characteristics (overload and short-circuit), dielectric strength and temperature rise. It defines the key indicators Icu (rated ultimate short-circuit breaking capacity) and Ics (rated service short-circuit breaking capacity), which underpin selective protection and person/equipment safety in distribution systems.
This part covers non-automatic switches, disconnectors and fuse-combination units, emphasising isolation function (visible break, clear OFF position, protection against inadvertent closing) and safety interlocking, used for on-load switching and isolation during maintenance.