BS EN 60909 — Short-Circuit Currents in Three-Phase A.C. Systems Standard Series (Current Calculation and Currents Through Earth)

Calculation of Currents and Currents During Double Line-to-Earth Short-Circuits (EN/IEC 60909 Series)

🔌 BS EN 60909 is the British Standard adopting, identically, the IEC 60909 European standard series for short-circuit current calculation in three-phase a.c. systems. Developed by IEC/TC 73 (Short-circuit currents), approved by CENELEC as EN 60909, and adopted in the UK by committee PEL/73, it sets the method for calculating short-circuit currents. Short-circuit current is a fundamental design parameter of power systems: it determines the breaking capacity and dynamic/thermal withstand of breakers, switches, busbars, and cables, and is the prerequisite for protection relay setting and grid operation analysis. This batch includes Part 0 (current calculation, 2016 edition) and Part 3 (currents during two separate simultaneous line-to-earth short-circuits and partial short-circuit currents through earth, 2010 edition with 2013 corrigendum).

💡 The IEC 60909 short-circuit calculation method is widely adopted in global power engineering practice; it corresponds to the “IEC 60909 method” in power system analysis software and is a common language for equipment selection and protection setting.

1. Scope and General Framework 📌

The BS EN 60909 series applies to short-circuit current calculation in three-phase a.c. systems, covering networks composed of generators, transformers, lines, and loads. The series structure is:

  • Part 0: Calculation of currents: definitions, equivalent circuits, and calculation methods (equivalent voltage source method) for various short-circuit types (three-phase, two-phase, single-phase line-to-earth, etc.).
  • Part 3: Currents during two separate simultaneous line-to-earth short-circuits and partial short-circuit currents flowing through earth: deals with two independent simultaneous earth faults and partial short-circuit currents returning through earth, important for earth-fault and earth-potential analysis.

Both documents carry ICS 17.220.01 / 29.020 / 29.240.20. BS EN 60909-0:2016 corresponds to IEC 60909-0:2016 (edition 2), superseding the 2001 edition; BS EN 60909-3:2010 (with IEC corrigendum September 2013) corresponds to IEC 60909-3:2009 (edition 3), superseding the 2003 edition.

⚠️ The accuracy of short-circuit current calculation directly affects the safety margin and economics of equipment selection: underestimation may lead to inadequate breaking capacity, while overestimation causes waste. Model correctly and consider impedance correction and pre-fault voltage.

2. Series Composition and Technical Points 🔧

StandardTitleFocusIEC EquivalentStatus
BS EN 60909-0:2016Part 0: Calculation of currentsEquivalent voltage source method, various short-circuit types, impedance correctionIEC 60909-0:2016Current (supersedes 2001)
BS EN 60909-3:2010Part 3: Double line-to-earth and partial short-circuit currents through earthDouble earth fault, earth-return current calculationIEC 60909-3:2009Current (with 2013 corrigendum)

1. Calculation of Currents (Part 0)

Part 0 gives a complete methodology for short-circuit current calculation, including:

  • Equivalent voltage source method: an equivalent voltage source at the short-circuit location, simplifying the handling of pre-fault load state and suitable for both manual and computer calculation.
  • Short-circuit current components: determination of the initial symmetrical short-circuit current I″k, peak value ip, d.c. component, and breaking current.
  • Impedance calculation and correction: modelling of generator, transformer, and line impedances, plus voltage regulation/coefficient corrections.
  • Short-circuit types: three-phase, two-phase, two-phase-to-earth, and single-phase line-to-earth short-circuit currents.

2. Currents Through Earth (Part 3)

Part 3 deals with two independent simultaneous earth faults and partial short-circuit currents flowing through earth: it describes the characteristics, equivalent circuits, and calculation methods for such faults, used for earth-fault analysis, earth-potential-rise assessment, and earthing system design.

💡 Analysis of short-circuit currents returning through earth is crucial for substation earthing grids, communication surge protection, and personnel safety: earth-potential rise from earth currents can endanger equipment and people.

3. Key Technical Requirements 🔬

Key technical points in short-circuit current calculation include:

  • Equivalent voltage source c·Un/√3: the magnitude of the equivalent voltage source at the fault point is determined by the voltage factor c and the nominal system voltage; c reflects system voltage deviation.
  • Impedance correction factors: generator and transformer impedances are corrected (e.g. KGS, KT) to account for saturation and tap position effects.
  • Maximum/minimum short-circuit currents: in practice, maximum values (for equipment thermal/dynamic withstand and breaking capacity) and minimum values (for protection sensitivity) are calculated separately.
  • Non-rotating loads and motors: large motors feed short-circuit current in the initial period, and must be included per the standard.
  • Calculation validity: the standard gives validity handling and error control requirements for both manual and computer calculation.
🚨 Short-circuit current calculation must be completed and documented during design: it is the common basis for breaker breaking capacity, busbar and cable dynamic/thermal withstand, earthing design, and protection setting. Missing or erroneous calculation can cause catastrophic failures.

4. Engineering Practice and Application 🛠️

  • 🔍 Data collection: gather system single-line diagram, source (grid/generator) parameters, transformer impedances, line parameters, and motor data.
  • 🔧 Modelling and calculation: build positive/negative/zero-sequence impedance networks using the equivalent voltage source method and calculate short-circuit currents at each fault point.
  • 📊 Equipment verification: use maximum short-circuit current to verify switchgear breaking capacity and dynamic/thermal withstand, and minimum current to verify protection sensitivity.
  • 📋 Documentation and review: produce a short-circuit current calculation report and re-verify when network topology changes (new sources/transformers).

5. Frequently Asked Questions ❓

❓ Q: Why are both maximum and minimum short-circuit currents calculated?
A: Maximum short-circuit current verifies equipment breaking capacity and dynamic/thermal withstand (ensuring equipment is not damaged), while minimum verifies protection device sensitivity (ensuring faults are reliably cleared); the two serve different purposes.
🔍 Q: What is the basic idea of the equivalent voltage source method?
A: The fault point is represented by an equivalent voltage source c·Un/√3 and the rest of the network by impedances, so short-circuit current can be calculated without detailed modelling of pre-fault load distribution — simple and sufficiently accurate for engineering.
📊 Q: What are the applications of Part 3?
A: Primarily for two simultaneous line-to-earth faults (e.g. double-point grounding at different points of a line) and partial short-circuit currents returning through earth, involving earthing grid design, earth-potential-rise assessment, and protection analysis.
💡 Q: What is the impedance correction factor?
A: Generator and transformer calculated impedances are multiplied by correction factors (e.g. KGS, KT) to account for saturation, tap position, and rated-parameter differences, making results closer to actual short-circuit currents.
🔒