BS EN 60898 — Circuit-Breakers for Overcurrent Protection for Household and Similar Installations Standard Series (AC and AC/DC Operation)

Circuit-Breakers for Overcurrent Protection for Household and Similar Installations (EN/IEC 60898 Series)

⚡ BS EN 60898 is the British Standard adopting the IEC 60898 European standard series for circuit-breakers for overcurrent protection for household and similar installations (commonly known as miniature circuit-breakers, MCBs). Developed by IEC/TC 23 (Electrical accessories), Subcommittee SC 23E, approved by CENELEC as EN 60898, and adopted in the UK by committee PEL/23 and its subcommittee PEL/23/1 (Circuit breakers and similar equipment for household use), the series covers overcurrent protection of distribution circuits in household and similar installations. It is one of the most widely used circuit-breaker standards in residential electrical installations.

💡 The circuit-breakers specified in BS EN 60898 are “circuit-protection-type” switching devices: they protect conductors according to their overcurrent tripping characteristics, preventing overheating and fire from overload and short-circuit, and are the core components of household distribution boards.

1. Scope and General Framework 📌

The BS EN 60898 series applies to circuit-breakers for overcurrent protection for household and similar installations, i.e. breakers with rated voltage generally not exceeding 440 V a.c. (some types up to 415 V etc.) intended for protection of distribution circuits in household and similar installations. The series structure is:

  • Part 1: Circuit-breakers for a.c. operation: ratings, tripping characteristics (types B/C/D etc.), breaking capacity, and test requirements for a.c. circuits.
  • Part 2: Circuit-breakers for a.c. and d.c. operation: supplements Part 1 with d.c. operation requirements, covering both a.c. and d.c. circuits.

Both documents carry ICS 29.120.50. BS EN 60898-1:2003+A13:2012 is derived from IEC 60898-1:2002, incorporating CENELEC amendments A11, A12, and A13 and corrigendum February 2004; BS EN 60898-2:2006 is derived from IEC 60898-2:2000+A1:2003 (modified) and includes Corrigendum No. 1.

⚠️ Division of labour between Part 1 and Part 2: Part 1 addresses pure a.c. circuits; Part 2 adds d.c. operation capability requirements. For projects with d.c. circuits (e.g. photovoltaic, d.c. distribution), select breakers built to Part 2.

2. Series Composition and Technical Points 🔧

StandardTitleFocusSourceStatus
BS EN 60898-1:2003+A13:2012Circuit-breakers for a.c. operationRatings, tripping characteristics, breaking capacity, testsIEC 60898-1:2002 (modified)Current (incl. A11/A12/A13)
BS EN 60898-2:2006Circuit-breakers for a.c. and d.c. operationSupplement to Part 1 for d.c. operationIEC 60898-2:2000+A1:2003 (modified)Current (incl. Corr. No. 1)

1. Circuit-Breakers for a.c. Operation (Part 1)

Part 1 specifies the general requirements for household and similar a.c. overcurrent protection circuit-breakers:

  • Ratings and marking: rated voltage, rated current, frequency, tripping characteristics (B, C, D, etc.), and breaking capacity (e.g. 6 kA, 10 kA).
  • Tripping characteristics: instantaneous and time-delay tripping current ranges; types B, C, and D suit different load types.
  • Constructional and mechanical requirements: contacts, mechanism, enclosure, and terminal requirements.
  • Test programme: temperature rise, tripping characteristics, dielectric performance, mechanical life, electrical life, breaking capacity, and reliability tests.
  • National annex: UK National Annex NA reproduces CENELEC Interpretation Sheets 1–4 as guidance.

2. Circuit-Breakers for a.c. and d.c. Operation (Part 2)

Part 2, based on Part 1, adds requirements specific to a.c. and d.c. operation, including d.c. breaking capacity, d.c. tripping characteristics, and the corresponding test methods, for applications requiring d.c. operation.

💡 Tripping characteristics are key to selection: type B for resistive loads and lighting, type C for general distribution and small motors, and type D for motors and transformers with high inrush currents.

3. Key Technical Requirements 🔬

Key technical requirements for household and similar circuit-breakers include:

  • Tripping characteristics (time-current characteristics): the standard specifies tripping time ranges for overloads (e.g. 1.13 and 1.45 times rated current) and short-circuits (e.g. 5 and 10 times rated current), ensuring discrimination and personal/equipment protection.
  • Breaking capacity: the breaker must be able to break the specified short-circuit current without failure; it should be no less than the prospective short-circuit current at the point of installation.
  • Temperature rise and heating: terminal and contact temperature rises at rated current must not exceed limits, preventing insulation ageing.
  • Dielectric performance and insulation: sufficient insulation strength between phases, phase-to-earth, and live parts versus accessible parts.
  • Mechanical and electrical life: performance retention after a specified number of operations.
🚨 Before installation, verify that the breaker’s breaking capacity is not less than the prospective short-circuit current at the installation point; otherwise contact welding, enclosure bursting, or even fire may occur on short-circuit. Never handle a suspect faulty breaker with bare hands while live.

4. Engineering Practice and Application 🛠️

  • 🔍 Selection: determine the tripping characteristic (B/C/D) by load type, the rated current by circuit calculated load, and the breaking capacity by short-circuit calculation; verify the number of poles and mounting mode.
  • 🔧 Installation: install breakers on compliant distribution board/din rail; tighten terminal connections to the manufacturer’s torque for reliable joints.
  • 📊 Protection coordination: verify discrimination between upstream and downstream breakers to avoid nuisance tripping; combine with residual current devices (RCD/RCBO) where necessary.
  • 📋 Test and maintenance: verify insulation and breaking capacity after installation, periodically inspect connections and operating mechanism, and replace when abnormal.

5. Frequently Asked Questions ❓

❓ Q: What is the difference between BS EN 60898 and BS EN 60947-2?
A: BS EN 60898 covers circuit-breakers for household and similar installations (residential); BS EN 60947-2 covers low-voltage switchgear for industrial use. Ratings, tests, and certification requirements differ, so they must not be freely interchanged.
⚡ Q: How are types B, C, and D chosen?
A: Type B trips instantaneously at 3 to 5 times rated current, for lighting and resistive loads; type C at 5 to 10 times, for general distribution; type D at 10 to 20 times, for motors and transformers with high inrush currents.
🔍 Q: Why is breaking capacity important?
A: On short-circuit, the fault current can far exceed rated current; if the breaking capacity is inadequate, the breaker cannot break reliably and may explode or cause fire. Determine it by short-circuit calculation.
📊 Q: Can a.c. circuit-breakers be used on d.c. circuits?
A: Generally no. D.c. arcs do not self-extinguish at current zero like a.c., requiring special arc-extinguishing design. Use breakers built to BS EN 60898-2 or the appropriate d.c. standard for d.c. circuits.
🔒