🔌 BS EN 60700 is the British Standards Institution series adopting European Standard EN 60700, identical to IEC 60700, which covers thyristor valves for high voltage direct current (HVDC) power transmission. HVDC transmission is key to long-distance, large-capacity, low-loss power transfer in cross-regional grid interconnection and offshore wind delivery, and the thyristor converter valve is the core equipment of a converter station. Part 1 specifies the electrical testing of thyristor valves; Part 2 specifies the terminology for thyristor valves. The series was prepared by Technical Committee PEL/22, Power electronics, and is an important basis for converter valve design, type testing, routine testing and acceptance.
The BS EN 60700 series is identical to IEC 60700, prepared by SC 22F “Power electronics for electrical transmission and distribution systems” of IEC/TC 22 “Power electronic systems and equipment”, and was adopted in the UK by Technical Committee PEL/22. Part 1 (2015 edition) supersedes the 1998+A2:2008 edition; Part 2 (2016 edition) is a first issue. The series applies to thyristor valves in HVDC systems, covering the electrical performance, test conditions and acceptance criteria of rectifier/inverter valves, together with a unified terminology system.
| Standard Number | Title | IEC Reference | Main Content |
|---|---|---|---|
| BS EN 60700-1:2015 | Thyristor valves for HVDC power transmission — Part 1: Electrical testing | IEC 60700-1:2015 | Types of electrical tests, test circuits, test conditions, test procedures and acceptance criteria |
| BS EN 60700-2:2016 | Thyristor valves for HVDC power transmission — Part 2: Terminology | IEC 60700-2:2016 | Unified definitions of valve and components, operating modes, tests and parameters |
Part 1 specifies the electrical tests to be performed on thyristor valves, mainly including type tests (e.g. insulation tests, operating tests, non-recovery/recovery overvoltage tests, transient current tests, fault current tests) and routine tests (e.g. auxiliary supply tests, control and protection function tests, fibre-optic and firing-system checks). The tests cover valve electrical performance under normal operation, transient overvoltage and short-circuit fault conditions.
Insulation tests verify the valve’s insulation withstand capability, including power-frequency, lightning impulse and switching impulse tests for earth insulation, phase-to-phase insulation and valve-terminal insulation. Test voltage levels are determined from system voltage and insulation coordination; during the test, the voltage distribution across thyristor levels and grading conditions should be monitored to confirm adequate insulation margin.
| Test Category | Property Assessed | Key Parameters | Typical Criterion |
|---|---|---|---|
| Insulation tests | Valve insulation withstand capability | Power-frequency, lightning/switching impulse voltage | No breakdown, no flashover, voltage distribution satisfactory |
| Operating tests | Valve performance at rated operating conditions | Rated voltage, current, firing angle | Correct conduction and extinction, losses within limits |
| Transient overvoltage tests | Valve withstand of switching overvoltages | Recovery/non-recovery overvoltage | Thyristor-level grading and protection act correctly |
| Fault current tests | Valve withstand of short-circuit fault current | Fault current magnitude and duration | No damage, protection functions act correctly |
| Auxiliary and control tests | Firing and protection system functions | Firing signal, protection settings | Firing sequence and protection logic correct |
Part 1 details the test circuit configurations (such as synthetic test circuits and back-to-back test circuits), test conditions (voltage, current, frequency, temperature, cooling conditions) and test procedures, with requirements for test records and judgement. Synthetic test circuits can simulate the high-voltage, large-current operating conditions of converter valves in the laboratory, and are a common means for type testing.
Part 2 establishes a unified terminology system for the converter valve field, covering key terms such as valve, valve arm, thyristor level, firing system, cooling system, operating modes (rectifier/inverter), switching angle and overvoltage protection. Unified terminology eliminates ambiguity in engineering collaboration and provides the basis for standard drafting of contracts, design documents and test reports.