BS EN 60044 — Instrument Transformers Standard Series (Combined, Transient Protective and Electronic)

Combined Transformers, Protective Current Transformers for Transient Performance, and Electronic Transformers

⚡ BS EN 60044 is the British adoption of the IEC 60044 series covering instrument transformers for measurement and protection purposes. The parts in this batch are: BS EN 60044-3:2003 (combined transformers, identical to IEC 60044-3:2002), BS EN 60044-6:1999 (protective current transformers for transient performance, derived by CENELEC from IEC 60044-6:1992 with common modifications), BS EN 60044-7:2000 (electronic voltage transformers, identical to IEC 60044-7:1999), and BS EN 60044-8:2002 (scan version). The series is entrusted to Technical Committee PEL/38 (Instrument transformers) and provides unified product requirements for measurement, metering and protection in generation, transmission, distribution, and high-voltage testing.

💡 Instrument transformers are both the “eyes” of measurement and the “shield” of protection in a power system: the measuring winding supplies accurate data for metering and monitoring, while the protection winding must faithfully reproduce the primary current under transient conditions such as short circuits. The BS EN 60044 parts address these two needs separately.

1. Series Overview and Structure 📌

The BS EN 60044 series follows the IEC 60044 numbering, with each part covering a different type of instrument transformer:

  • BS EN 60044-3:2003: combined transformers — current and voltage transformers integrated within a single insulation structure, providing simultaneous current and voltage signals. Used mainly in compact installations such as GIS and indoor switchgear.
  • BS EN 60044-6:1999: protective current transformers for transient performance — defines error and performance requirements for protection CTs under transient (dynamic) conditions, fundamental to correct relay operation.
  • BS EN 60044-7:2000: electronic voltage transformers (EVTs) — for new voltage sensing devices based on electronic and optical technology.
  • BS EN 60044-8:2002: electronic current transformers (scan version).
⚠️ Some source documents (such as 60044-8) are scanned copies with limited extractable text; the corresponding content here is based on public domain knowledge. For formal selection and testing, refer to the official BSI published versions.

2. Combined Transformers (Part 3) 🔧

BS EN 60044-3 sets general requirements for combined transformers, covering ratings, accuracy classes, temperature rise, insulation, testing and marking. A combined transformer integrates a current transformer (CT) and a voltage transformer (VT/PT) in a single unit. Key technical aspects include:

  • Ratings and marking: rated primary/secondary currents and voltages, rated secondary output, and combinations of measuring and protection accuracy classes according to use.
  • Accuracy classes: measuring transformers are assessed by ratio error and phase displacement; protection transformers by composite error; the current and voltage parts each satisfy their own class requirements.
  • Insulation and temperature rise: winding insulation levels are set by system voltage; temperature rise is verified at rated burden.
  • Testing: type tests (temperature rise, short-time thermal current, dynamic stability) and routine tests (insulation resistance, polarity, error).
✅ By sharing insulation and primary conductor arrangements, combined transformers significantly save substation space and cost and are the mainstream solution for compact and indoor switchgear (especially GIS).

3. Protective Current Transformers for Transient Performance (Part 6) 🛡️

BS EN 60044-6 specifically addresses the transient performance of protection current transformers. When a short circuit occurs, the primary current contains a large DC offset component with a decaying time constant; ordinary measuring CTs may saturate and seriously distort the secondary current, causing protection maloperation or failure to operate. The standard therefore specifies:

  • Transient accuracy classes: classes are defined according to fault type and reproduction requirement (e.g. symmetrical/asymmetrical short circuit, with or without residual flux), characterized by defined error limits.
  • Core and air gap: to suppress residual flux and accelerate flux decay, transient CTs often use cores with air gaps (linear, low remanence designs).
  • Rated symmetrical/asymmetrical short-circuit current factors: define the ability to reproduce primary current without saturation under rated conditions.
  • Verification: specified transient tests (simulating primary time constant and DC component) verify error and saturation behaviour.
🚨 Transient performance is critical for high-speed protection such as differential and busbar protection: if the CT saturates early during a fault transient, protection may misjudge. Selection must verify the CT transient capability against the maximum system fault current and decay time constant.

4. Electronic Transformers (Parts 7/8) 💡

BS EN 60044-7:2000 specifies requirements for electronic voltage transformers, which no longer rely on conventional electromagnetic coupling but use sensors (capacitive dividers, optical techniques) and electronic processing units to provide an analogue or digital output proportional to the primary voltage. Electronic transformers must also satisfy accuracy, insulation, temperature-rise and EMC requirements. It should be noted that the UK National Committee voted against publication and submitted objections, including:

  • the term “Transformers” in the title was considered inappropriate, with “Transducers” recommended instead;
  • the inherent wide bandwidth of some non-conventional sensors is ignored;
  • insufficient attention is given to the effects of vibration on sensors installed as integral parts of switchgear;
  • digital outputs are not standardized, and temperature-rise test acceptance and modality are not detailed.
💡 Mature application of electronic transformers requires addressing wideband response, vibration resistance, and digital-interface standardization — exactly the focus of the later IEC 61869 series (new generation of instrument transformers).

5. Engineering Application 🛠️

The parts of BS EN 60044 are widely used in the following scenarios:

  • Metering and monitoring: combined transformers for current/voltage measurement and energy metering in substation switchgear;
  • Protection: transient-performance CTs in line, transformer, busbar differential protection, and breaker-failure protection circuits;
  • Digital substations: electronic voltage/current transformers support process-layer digital sampling and, with merging units, IEC 61850 digital secondary systems;
  • High-voltage testing: measuring transformers provide accurate voltage and current signals for HV test circuits.
⚠️ When selecting a transformer, verify simultaneously: rated primary/secondary values, the accuracy-class combination (measuring/protection), rated output (avoid exceeding the rated burden leading to error), insulation level, and metering requirements (trade settlement requires verified metering CTs).

6. Frequently Asked Questions ❓

❓ Q: What is the difference between measuring and protection accuracy classes?
A: Measuring classes are limited by ratio error and phase displacement to ensure accurate metering under normal operation; protection classes are limited by composite error under fault current to ensure reliable operation of protective devices. The criteria and applications differ.
❓ Q: Why do transient protective CTs require special design?
A: Because short-circuit currents contain DC components that can saturate the core and distort the secondary current. Transient CTs use air-gapped cores, saturation margins, and defined transient error classes so that protection receives a faithful waveform during the first few hundred milliseconds of a fault.
❓ Q: Can the voltage and current parts of a combined transformer be selected with different accuracy classes?
A: Yes. The voltage and current parts can each be specified for their intended use (e.g. current part 0.2S for metering and 5P for protection, voltage part 0.5), but the whole unit must still meet the general requirements of Part 3.
🔍 Q: What are the advantages and limitations of electronic transformers versus conventional ones?
A: Advantages include wide dynamic range, broad bandwidth, no magnetic saturation, and easy digitization; limitations are that early standards were incomplete on digital output, vibration and temperature-rise acceptance, requiring stricter environmental and EMC verification, and engineering practice and interoperability are still evolving.
🔧 Q: What is the effect of an excessive secondary burden on a transformer?
A: When the secondary burden (lead impedance plus input impedance of instruments/protection) exceeds the rated output, errors increase significantly — affecting metering accuracy for measuring classes and possibly reducing transient reproduction for protection classes. The secondary circuit burden should be calculated with margin.
🔒