💧 BS EN 16297 is a European standard developed by CEN and adopted by BSI, specifying the testing and calculation of the Energy Efficiency Index (EEI) for glandless circulators — rotodynamic pumps with integrated motor and wet rotor, needing no mechanical shaft seal. Glandless circulators are widely used for water circulation in heating, air-conditioning and domestic hot-water systems and form a significant part of building energy use. The series has three parts: Part 1 gives general requirements and procedures for testing and calculating the EEI, Part 2 covers EEI calculation for standalone circulators, and Part 3 covers EEI for circulators integrated in products, supporting compliance with EU pump energy-regulation (ErP).
💡 Glandless circulators run continuously all year, so their energy use is a significant share of building heating consumption. The EEI is the key indicator of a circulator’s efficiency: the lower the EEI, the more efficient the pump. EU regulation uses EEI thresholds to drive replacement of inefficient circulators.
1. Scope and Series Framework 📌
This series applies to glandless circulators (wet-rotor circulators), i.e., rotodynamic pumps where the motor and pump rotor are coaxial and the medium cools the motor, including standalone circulators and circulators integrated in products (e.g., gas boilers, heat pumps).
| Standard | Part | Subject | Core content |
| BS EN 16297-1:2012 | Part 1 | General requirements and testing procedures | Terms, symbols, units, testing procedures and EEI calculation general rules (supersedes EN 1151-1) |
| BS EN 16297-2:2012 | Part 2 | EEI for standalone circulators | Calculation of the energy efficiency index for standalone (external) circulators |
| BS EN 16297-3:2012 | Part 3 | EEI for circulators integrated in products | Calculation of the energy efficiency index for circulators integrated in products |
The series was prepared with UK participation in Technical Committee MCE/6 (Pumps and pump testing), ICS 23.080 (Pumps). Parts 1 and 2 supersede the withdrawn BS EN 1151-1:2006.
⚠️ This series addresses the EEI of glandless circulators. For ordinary centrifugal pumps with mechanical shaft seals, energy assessment should follow other standards (e.g., ISO 9906), not this series directly.
2. Series Structure and Technical Essentials 🔧
2.1 General requirements and testing procedures (Part 1)
Part 1 sets general requirements, terms and symbols, units, and the overall procedures for testing and EEI calculation of glandless circulators. The standard defines test rigs, measuring instruments, test conditions and data processing, providing a uniform testing basis for Parts 2 and 3 and ensuring comparability of results between pumps and laboratories.
2.2 EEI calculation for standalone circulators (Part 2)
Part 2 specifies the EEI calculation for standalone circulators. A standalone circulator is installed as an individual product in a heating/air-conditioning system; its EEI is calculated from the power-flow relationship at a standard reference profile, reflecting the weighted energy use under a typical load cycle.
2.3 EEI for circulators integrated in products (Part 3)
Part 3 specifies the EEI calculation for circulators integrated in products. An integrated circulator (e.g., inside a gas boiler or heat pump) cannot be tested alone, so testing and calculation are performed under the complete product’s operating conditions; the standard gives the corresponding test and rating methods so the energy efficiency of the integrated pump can be quantified.
✅ The three parts form a complete energy-efficiency assessment system: Part 1 unifies the testing basis, Part 2 addresses standalone products, and Part 3 addresses integrated products, together supporting consistent, comparable and verifiable EEI assessment of glandless circulators.
3. Key Technical Requirements 🛡️
The series emphasises the following key points:
- Energy Efficiency Index (EEI): based on the power-flow relationship at a standard reference profile; the lower the EEI, the more efficient the pump — the core metric for regulatory compliance and product labelling.
- Reference profile and load cycle: circulator efficiency is assessed against a typical heating/air-conditioning load cycle (reference profile), reflecting weighted energy use in real operation rather than efficiency at a single operating point.
- Test rig and measurement: the standard sets requirements for test rigs, flow/head/power measuring instruments, test medium and data processing to ensure measurement accuracy and repeatability.
- Speed control and control behaviour: modern circulators use variable-speed control and pressure/temperature control; the standard requires testing and calculation to reflect control behaviour, avoiding assessment at full-load point only.
- Standalone vs integrated: standalone and integrated pumps have different testing and calculation methods; select the corresponding part by product form.
- Reporting and labelling: EEI results should be documented in a report and labelled as required, for market surveillance and user reference.
🚨 The key to EEI assessment is “representing actual operation”: assessing by full-load single-point efficiency alone overestimates the true efficiency of variable-speed pumps. The standard requires assessment based on load cycles and control behaviour; tests must follow the standard reference profile and procedures, otherwise results are not comparable.
4. Engineering Practice 🛠️
Glandless circulator EEI is widely used in building services:
- Heating-system circulators: water circulation pumps in residential and public buildings, selected and replaced for high efficiency by EEI.
- Air-conditioning system circulators: energy assessment and retrofit of chilled-water/condenser water circulators.
- Domestic hot-water circulation: EEI assessment and efficient selection of hot-water circulation pumps.
- Product-integrated applications: EEI assessment and whole-product energy labelling of built-in circulators in gas boilers, heat pumps, etc.
In practice, selection and assessment should verify: matching of the circulator’s application duty and reference load cycle, testing and calculation per the standard procedures, correct distinction between standalone and integrated pumps, and completeness and compliance of EEI reports and product labelling.
💡 Selection tip: with the required flow and head satisfied, prefer high-efficiency circulators with lower EEI; check that the product provides the standard EEI test report and labelling, and fit reasonable variable-speed and differential-pressure control in the system to fully realise energy-saving potential.
5. Frequently Asked Questions ❓
❓ Q: What is a glandless circulator?
A: A glandless circulator is a rotodynamic pump with integrated motor and wet rotor, cooled by the medium and needing no mechanical shaft seal, widely used in heating, air-conditioning and hot-water systems.
❓ Q: What does the Energy Efficiency Index (EEI) represent?
A: EEI is an index of a circulator’s efficiency, calculated from weighted energy use under a standard reference profile and load cycle. The lower the EEI, the more efficient the pump; it is the core metric for compliance and labelling.
❓ Q: Why is full-load efficiency alone not sufficient?
A: Circulators operate at varying load, and variable-speed pumps are most efficient at part load. The standard requires assessment of weighted energy use over a load cycle to avoid overestimating actual efficiency.
🔍 Q: How does assessment differ between standalone and integrated circulators?
A: Standalone pumps are tested and calculated per Part 2 as separate products; integrated pumps inside a complete product cannot be tested alone and are tested and calculated per Part 3 under the product’s operating conditions.